Protect yourself against future threats.
-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA256 =========================================================================== AUSCERT External Security Bulletin Redistribution ESB-2018.0695 Siemens SIPROTEC 4, SIPROTEC Compact, DIGSI 4, and EN100 Ethernet Module 9 March 2018 =========================================================================== AusCERT Security Bulletin Summary --------------------------------- Product: Siemens SIPROTEC 4, SIPROTEC Compact, DIGSI 4, and EN100 Ethernet Module Publisher: ICS-CERT Operating System: Network Appliance Impact/Access: Access Privileged Data -- Remote/Unauthenticated Modify Arbitrary Files -- Remote/Unauthenticated Resolution: Patch/Upgrade CVE Names: CVE-2018-4840 CVE-2018-4839 Original Bulletin: https://ics-cert.us-cert.gov/advisories/ICSA-18-067-01 - --------------------------BEGIN INCLUDED TEXT-------------------- Advisory (ICSA-18-067-01) Siemens SIPROTEC 4, SIPROTEC Compact, DIGSI 4, and EN100 Ethernet Module Original release date: March 08, 2018 Legal Notice All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/. CVSS v3 7.5 ATTENTION: Exploitable remotely/low skill level to exploit. Vendor: Siemens Equipment: SIPROTEC 4, SIPROTEC Compact, DIGSI 4, and EN100 Ethernet module Vulnerabilities: Missing Authentication for Critical Function, Inadequate Encryption Strength AFFECTED PRODUCTS Siemens reports that the vulnerabilities affect the following products: DIGSI 4: All versions prior to V4.92, EN100 Ethernet module IEC 61850 variant: All versions prior to V4.30, EN100 Ethernet module PROFINET IO variant: All versions, EN100 Ethernet module Modbus TCP variant: All versions, EN100 Ethernet module DNP3 variant: All versions, EN100 Ethernet module IEC 104 variant: All versions, SIPROTEC 4 7SJ66: All versions prior to V4.30. Only affected by CVE-2018-4839, SIPROTEC Compact 7SJ80: All versions prior to V4.77. Only affected by CVE-2018-4839, SIPROTEC Compact 7SK80: All versions prior to V4.77. Only affected by CVE-2018-4839, Other SIPROTEC Compact relays: All versions. Only affected by CVE-2018-4839, and Other SIPROTEC 4 relays: All versions. Only affected by CVE-2018-4839. IMPACT Successful exploitation of these vulnerabilities could allow an attacker to upload a modified device configuration that could overwrite access authorization passwords, or allow an attacker to capture certain network traffic that could contain authorization passwords. MITIGATION Siemens has provided the following updates for mitigations: DIGSI 4: Update to V4.92 which can be located here: https://support.industry.siemens.com/cs/ww/en/view/109740980 EN100 Ethernet module IEC 61850 variant: Update to V4.30 which can be located here: https://support.industry.siemens.com/cs/us/en/view/109745821 SIPROTEC 4 7SJ66: Update to V4.30 which can be located here: https://support.industry.siemens.com/cs/us/en/ view/109743555 SIPROTEC Compact 7SJ80:Update to V4.77 which can be located here: https://support.industry.siemens.com/cs/us/en/view/109742699 SIPROTEC Compact 7SK80: Update to V4.77 which can be located here: https://support.industry.siemens.com/cs/us/en/view/109742712 For all other affected products, Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk. As a general security measure, Siemens strongly recommends protecting network access with appropriate mechanisms (e.g., firewalls, segmentation, VPN). It is advised that users configure the environment according to Siemens operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines to Secure Substations and Defense in Depth can be found at: https://www.siemens.com/gridsecurity For further inquiries on vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories For more information on these vulnerabilities and associated software updates, please see Siemens security notification SSA-203306 on their website: https://cert-portal.siemens.com/productcert/pdf/ssa-203306.pdf NCCIC recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet. Locate control system networks and remote devices behind firewalls, and isolate them from the business network. When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices. NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents. No known public exploits specifically target these vulnerabilities. VULNERABILITY OVERVIEW MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306 Successful exploitation of this vulnerability could allow an attacker to upload a modified device configuration, allowing an overwrite of access authorization passwords. CVE-2018-4840 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N). INADEQUATE ENCRYPTION STRENGTH CWE-326 Successful exploitation of this vulnerability could allow an attacker with local access to the engineering system or in a privileged network position to capture certain network traffic, and possibly reconstruct access authorization passwords. CVE-2018-4839 has been assigned to this vulnerability. A CVSS v3 base score of 4.0 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:C/C:L/I:N/A:N). RESEARCHER Ilya Karpov and Dmitry Sklyarov from Positive Technologies reported these vulnerabilities to Siemens. BACKGROUND Critical Infrastructure Sector: Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Germany Contact Information For any questions related to this report, please contact the NCCIC at: Email: NCCICCUSTOMERSERVICE@hq.dhs.gov Toll Free: 1-888-282-0870 For industrial control systems cybersecurity information: http://ics-cert.us-cert.gov or incident reporting: https://ics-cert.us-cert.gov/Report-Incident? The NCCIC continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product. - --------------------------END INCLUDED TEXT-------------------- You have received this e-mail bulletin as a result of your organisation's registration with AusCERT. The mailing list you are subscribed to is maintained within your organisation, so if you do not wish to continue receiving these bulletins you should contact your local IT manager. If you do not know who that is, please send an email to auscert@auscert.org.au and we will forward your request to the appropriate person. NOTE: Third Party Rights This security bulletin is provided as a service to AusCERT's members. As AusCERT did not write the document quoted above, AusCERT has had no control over its content. The decision to follow or act on information or advice contained in this security bulletin is the responsibility of each user or organisation, and should be considered in accordance with your organisation's site policies and procedures. AusCERT takes no responsibility for consequences which may arise from following or acting on information or advice contained in this security bulletin. NOTE: This is only the original release of the security bulletin. It may not be updated when updates to the original are made. If downloading at a later date, it is recommended that the bulletin is retrieved directly from the author's website to ensure that the information is still current. Contact information for the authors of the original document is included in the Security Bulletin above. If you have any questions or need further information, please contact them directly. Previous advisories and external security bulletins can be retrieved from: https://www.auscert.org.au/bulletins/ =========================================================================== Australian Computer Emergency Response Team The University of Queensland Brisbane Qld 4072 Internet Email: auscert@auscert.org.au Facsimile: (07) 3365 7031 Telephone: (07) 3365 4417 (International: +61 7 3365 4417) AusCERT personnel answer during Queensland business hours which are GMT+10:00 (AEST). On call after hours for member emergencies only. =========================================================================== -----BEGIN PGP SIGNATURE----- Comment: http://www.auscert.org.au/render.html?it=1967 iQIVAwUBWqI6eIx+lLeg9Ub1AQh+7w//dADRLsRkDfxwb2/a80Tyv5xVL8w9qDaD oPEsfkknyl0CylE4SOytun3VWOwsOwi/+T0wCFqpwkMENUDhuy8rSEGMllqHrMOZ 69g/EVmmWwNtVrRWNd48SQ8y/N5bfcbK/cBctRoO0K3MkpoIi2331RQ5vVHSlUkH FkIf/M88hw7SxsBfxfZwgNw/W+yXIug0XiC2dpCevQQP1JMoG3PEleQiCgU3Zn8x yqgjLGMsZZcyJxRUad87wZuxHi+vYgUbQTFgiVSvUDqvD/PZQndAevpmBWPh3CZH iZLCgpNxcmO02IEXs7d3hqhqrMv+eoeRlJPc4aXMAYn6l3/8ueA4Sej9virvrs7m yCVRBCcFCatXtGshgVJ8ohYSO/ZP3zz3pQHbg0ywNy1iiPGbPMW95gphkfAvg8uM 4cMMaFFkklnQi+wsOk+FlMS5fJNYp9IlE+ObJJWUn22/WGERHbhzmCe+pnSmnoh8 nmW4P0nYkdvxiDpMwi7+R1PYow+PftEuSJhVADb2S4l1KtCVrzzeOCXRBpz1LNDh cw8mmAxcvaYbheAH6g2kf80qFi9ljt2/HiK8QoPsn4XtY3Ycl6zTlalZzlg52Gj4 FyeI0iwMbt1W+TmmF7HZwtTgO8G5o92E7JOUd5XU2wSPSzhCSmrjPS/FAsyGZ9JD +Z3QLWdzg9A= =2nux -----END PGP SIGNATURE-----