-----BEGIN PGP SIGNED MESSAGE-----
Hash: SHA256

===========================================================================
             AUSCERT External Security Bulletin Redistribution

                               ESB-2022.4034
      Advisory (icsa-22-223-05) Siemens SICAM A8000 Web Server Module
                              12 August 2022

===========================================================================

        AusCERT Security Bulletin Summary
        ---------------------------------

Product:           Siemens SICAM A8000 Web Server Module
Publisher:         ICS-CERT
Operating System:  Network Appliance
Resolution:        Mitigation
CVE Names:         CVE-2021-46304  

Original Bulletin: 
   https://us-cert.cisa.gov/ics/advisories/icsa-22-223-05

Comment: CVSS (Max):  4.3 CVE-2021-46304 (CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:N)
         CVSS Source: ICS-CERT
         Calculator   https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:N

- --------------------------BEGIN INCLUDED TEXT--------------------

ICS Advisory (ICSA-22-223-05)

Siemens SICAM A8000 Web Server Module

Original release date: August 11, 2022

Legal Notice

All information products included in https://us-cert.cisa.gov/ics are provided
"as is" for informational purposes only. The Department of Homeland Security
(DHS) does not provide any warranties of any kind regarding any information
contained within. DHS does not endorse any commercial product or service,
referenced in this product or otherwise. Further dissemination of this product
is governed by the Traffic Light Protocol (TLP) marking in the header. For more
information about TLP, see https://us-cert.cisa.gov/tlp/ .



1. EXECUTIVE SUMMARY

  o CVSS v3 4.3
  o ATTENTION: Exploitable remotely/low attack complexity
  o Vendor: Siemens
  o Equipment: SICAM A8000 CP-8000, CP-8021, CP-8022
  o Vulnerability: Improper Access Control

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow unauthenticated
access to the web interface of the affected web server.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens has reported that this vulnerability affects the following SICAM A8000
Web Server Module products and versions:

  o CP-8000 MASTER MODULE WITH I/O -25/+70C (6MF2101-0AB10-0AA0): All Versions
  o CP-8000 MASTER MODULE WITH I/O -40/+70C (6MF2101-1AB10-0AA0): All Versions
  o CP-8021 MASTER MODULE (6MF2802-1AA00): All Versions
  o CP-8022 MASTER MODULE WITH GPRS (6MF2802-2AA00): All Versions

The affected protocol firmware utilized with the web server modules includes
the following:

  o AGPMT0 (AGP Master)
  o DNPiT1 (DNP3 TCP/IP Server)
  o DNPiT2 (DNP3 TCP/IP Client)
  o DNPMT0 (DNP3 Master seriell)
  o DNPST0 (DNP3 Slave seriell)
  o ET83 (61850 Ed.1)
  o ET85 (61850 Ed.2)
  o MBCiT0 (MODBUS TCP/IP Client)
  o MBSiT0 (MODBUS TCP/IP Server)
  o MODMT2 (MODBUS Master seriell)
  o OPUPT0 (OPCUA Pub/Sub)
  o OPUPT1 (Mindconnect)

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER ACCESS CONTROL - CWE-284

The vulnerability could allow attackers to activate a web server module,
allowing unauthorized access to its web pages. This could allow an attacker to
retrieve debug-level information from the component such as internal network
topology or connected systems.

CVE-2021-46304 has been assigned to this vulnerability. A CVSS v3 base score of
4.3 has been assigned; the CVSS vector string is ( AV:N/AC:L/PR:N/UI:R/S:U/C:L/
I:N/A:N ).

3.3 BACKGROUND

  o CRITICAL INFRASTRUCTURE SECTORS: Energy
  o COUNTRIES/AREAS DEPLOYED: Worldwide
  o COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

CybExer Technologies reported this vulnerability to Siemens.

4. MITIGATIONS

Siemens provided the following updates to the vulnerabilities for the following
products affected:

  o CP-8000 MASTER MODULE WITH I/O -25/+70C (6MF2101-0AB10-0AA0): There is
    currently no fix available
  o CP-8000 MASTER MODULE WITH I/O -40/+70C (6MF2101-1AB10-0AA0): There is
    currently no fix available
  o CP-8021 MASTER MODULE (6MF2802-1AA00): There is currently no fix available
  o CP-8022 MASTER MODULE WITH GPRS (6MF2802-2AA00): There is currently no fix
    available

Siemens has identified the following workarounds and mitigations for users to
reduce risk:

  o Operate the affected web server module only when required and apply the
    security instructions provided in the updated manual.

Siemens recommends users apply General Security Recommendations .

As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends users configure the
environment according to the Siemens operational guidelines for industrial
security and follow the recommendations in the product manuals.

For additional information, please refer to Siemens Security Advisory
SSA-185638 .

CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:

  o Minimize network exposure for all control system devices and/or systems,
    and ensure they are not accessible from the Internet .
  o Locate control system networks and remote devices behind firewalls and
    isolate them from the business network.
  o When remote access is required, use secure methods, such as Virtual Private
    Networks (VPNs), recognizing VPNs may have vulnerabilities and should be
    updated to the most current version available. Also recognize VPN is only
    as secure as its connected devices.

CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices
on the ICS webpage on cisa.gov . Several recommended practices are available
for reading and download, including Improving Industrial Control Systems
Cybersecurity with Defense-in-Depth Strategies .

Additional mitigation guidance and recommended practices are publicly available
on the ICS webpage on cisa.gov in the Technical Information Paper,
ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies .

Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

For any questions related to this report, please contact the CISA at:

Email: CISAservicedesk@cisa.dhs.gov
Toll Free: 1-888-282-0870

CISA continuously strives to improve its products and services. You can help by
choosing one of the links below to provide feedback about this product.

- --------------------------END INCLUDED TEXT--------------------

You have received this e-mail bulletin as a result of your organisation's
registration with AusCERT. The mailing list you are subscribed to is
maintained within your organisation, so if you do not wish to continue
receiving these bulletins you should contact your local IT manager. If
you do not know who that is, please send an email to auscert@auscert.org.au
and we will forward your request to the appropriate person.

NOTE: Third Party Rights
This security bulletin is provided as a service to AusCERT's members.  As
AusCERT did not write the document quoted above, AusCERT has had no control
over its content. The decision to follow or act on information or advice
contained in this security bulletin is the responsibility of each user or
organisation, and should be considered in accordance with your organisation's
site policies and procedures. AusCERT takes no responsibility for consequences
which may arise from following or acting on information or advice contained in
this security bulletin.

NOTE: This is only the original release of the security bulletin.  It may
not be updated when updates to the original are made.  If downloading at
a later date, it is recommended that the bulletin is retrieved directly
from the author's website to ensure that the information is still current.

Contact information for the authors of the original document is included
in the Security Bulletin above.  If you have any questions or need further
information, please contact them directly.

Previous advisories and external security bulletins can be retrieved from:

        https://www.auscert.org.au/bulletins/

===========================================================================
Australian Computer Emergency Response Team
The University of Queensland
Brisbane
Qld 4072

Internet Email: auscert@auscert.org.au
Facsimile:      (07) 3365 7031
Telephone:      (07) 3365 4417 (International: +61 7 3365 4417)
                AusCERT personnel answer during Queensland business hours
                which are GMT+10:00 (AEST).
                On call after hours for member emergencies only.
===========================================================================
-----BEGIN PGP SIGNATURE-----
Comment: https://auscert.org.au/gpg-key/
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=aHU4
-----END PGP SIGNATURE-----